SYSTEM INFORMATION
6. VOICE COMMUNICATIONS
6.1.1. Furnish and install a microprocessor-controlled integrated security and voice
communications system with all conduit, wire, outlets, and equipment as
shown on the drawings and as herein specified to provide a complete sound,
program distribution, and voice intercommunications system in the building.
6.1.2. Furnish and install the required number of Display Administrative Console
(DA1) with all conduit, wire, outlets, and equipment as shown on the drawings.
6.1.3. All field wiring shall be standard CAT-5 type terminated with RJ45 connectors.
Systems that do not use CAT-5 wire shall not be considered.
7. SYSTEM COMPONENTS
7.1.1. The CareHawk CH1000 is a distributed, multi-channel, microprocessor-
controlled security communication system. The system architecture shall allow
for Security Switching Cards (SS16) that contains 16 audio ports to be
remotely installed up to 2500 feet from the central cabinet. Each SS16 shall
only require one CAT5 wire run back to the central cabinet. The system shall
provide one independent intercom channels between any DA1 and
loudspeakers. One additional simultaneously operating channel shall be
provided for distribution of audio program material.
7.1.2. The system shall be capable of providing integration to third-party PBX
systems over an analog CO port, allowing operators to handle calls from
telephones connected to the PBX system, as well as DA1 telephone and
intercom calls.
7.1.3. The system shall be capable of providing individual control of inputs from and
outputs to external devices.
7.1.4. Rooms shall be equipped with call-in buttons. Call-ins from rooms shall allow
for a minimum of two priority levels. Upon arrival at the designated DA1 the
call shall be visually displayed and audibly annunciated. The system shall be
capable of accepting up to sixteen call-in devices per SS16 circuit, each with
different priorities and destination locations, over the same pair of wires.
7.1.5. The system shall have the capability for modular capacities of 128 audio ports
and 8 DA1s.
7.1.6. Systems that are not capable of being distributed on a modular basis, or are
not expandable or require replacement of any previously installed equipment
in order to facilitate expansion shall not be acceptable.
All Specifications are Subject to Change CareHawk 5